INSULATION RANGES |
MIT481/2 |
MIT485/2 |
50 V / 100 V / 250 V / 500 V |
• |
• |
Variable 10 V to 500 V |
|
• |
ΩA button (Leakage) |
• |
• |
Lock button on MΩ |
• |
• |
REN Telephone count
(discharge) |
• |
• |
> 500 V Gated Operation |
• |
• |
Continuity 0.01 - 10 M |
• |
• |
Isc: 200 mA R = 4Ω |
• |
• |
Isc 20 mA |
• |
• |
Difference measurement [REL] |
• |
• |
Lead null (<10 ) |
• |
• |
AC / DC Volts 600 V |
• |
• |
mV AC / DC range |
• |
• |
TRMS |
• |
• |
Frequency measurement
15 - 400 Hz |
• |
• |
Input impedance |
10 MΩ |
10 MΩ |
Capacitance 0.1 nF - 10 ΩF |
• |
• |
Distance by ΩF (Open loop) |
• |
• |
REN calculation |
• |
• |
Current measurement mA AC/DC |
• |
• |
PASS/FAIL on limit alarms |
|
• |
A/B/E or T/R/G switching |
• |
• |
Number of terminals |
3 |
3 |
On board memory |
• |
• |
Bluetooth ® and software |
|
• |
Recharger ready |
|
• |
AA Alkaline or NiMH |
Both |
Both |
CAT IV / 600V |
• |
• |
Silicone leads (R,B,G) |
• |
• |
Switched probe supplied |
• |
• |
SPECIFICATION |
All quoted accuracies are at +20 °C. |
Test voltage |
Nominal |
MIT481/2 and MIT485/2
50 V, 100 V, 250 V, 500 V |
Insulation accuracy |
|
50 Volts. 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ
100 Volts. 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ
250 Volts. 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ
500 Volts. 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ |
Service Error: BS EN 61557-2 (2007). |
50V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.5%
100V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3%
250V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3%
500V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% |
Display range |
Analogue: 1 GΩ full scale |
Resolution |
0.1 kΩ |
Short circuit/charge current |
2 mA +0% -50% to
EN 61557-2 (2007) |
Open circuit voltage
insulation |
-0% +2% ± 2 V |
Test current |
1 mA at min. pass value of
insulation to a maximum of 2 mA
max.
EN61557 Operating range:
0.10 MΩ to 1.0 0GΩ |
Leakage Current |
10% ±3 digits |
Timer control |
Countdown timer 60 second |
Note |
Above speci?cations only apply
when high quality silicone leads
are being used. |
Continuity range |
0.01 Ω to 1.0 MΩ |
Continuity accuracy |
± 3% ± 2 digits (0 to 100 Ω)
±5% ±2 digits (>100 Ω- 500 kΩ)
(>500 kΩ - 1 MΩ unspeci?ed)
Service Error: BS EN 61557-4
(2007) - ± 2.0%, 0.1Ω - 2Ω
± 6.8% |
Open circuit voltage |
5 V ± 1 V |
Test current |
200 mA (–0 mA +20 mA)
(0.01 Ω to 4 Ω) |
Lead resistance |
Nulling up to 10 Ω |
Voltage range |
AC: 10 mV to 600 V TRMS
sinusoidal (15 Hz to 400 Hz)
DC: 10 mV to 600 V |
Volt range accuracy |
AC: ± 2% ± 2 digits
DC: ± 2% ± 2 digits
Service Error: BS EN 61557-1
(2007) - ± 2.0% ± 2d,
0V - 300Vac/dc ± 5.1% |
Waveform |
Unspeci?ed range:
0 – 10 mV (15 to 400 Hz)
For non-sinusoidal waveforms
additional specifications apply:
Non-sinusoidal waveforms:
±3% ± 2 digits >100 mV
to 600 V TRMS
±8% ± 2 digits 10 mV to
100 mV TRMS |
Default voltmeter |
Operates at > 25 volts ac or dc on
any range except OFF |
Frequency measurement
range |
15 Hz - 400 Hz |
Frequency measurement
accuracy |
±0.5% ± 1 digit |
Capacitance range |
0.1 nF to 10 μF |
Accuracy |
± 5.0% ± 2 digits ( 1 nF-10 μF) |
Cable coefficient |
40n F/ km to 70nF / km |
Unit of measure |
50nF / km |
Storage capacity |
>1000 test results |
Data download |
Bluetooth ® wireless
Bluetooth ® Class II |
Range |
up to 10 m |
Power supply |
6 x 1,5 V cells
type IEC LR6 (AA, MN1500, HP7,
AM3 R6HP) Alkaline
6 x 1,2 V NiMH rechargeable cells
may be used. |
Battery life |
3000 insulation tests with duty
cycle of 5 sec ON /55 sec OFF @
500 V into 500 kΩ
Charger (Optional): 12-15 V dc
(accessory interface) |
Dimensions |
228 mm x 108 mm x 63 mm
(9.00 in x 4.25 in x 2.32 in) |
Weight |
800 g |
Weight (instrument and
case) |
1.75 kg (3.86 lb) |
Fuse |
Use only 2 x 500 mA (FF) 1000
V 32 x 6 mm ceramic fuse of
high breaking capacity HBC 30
kA minimum. Glass fuses MUST
NOT be fitted. |
Safety protection |
The instruments meet
EN 61010-1 (1995) to 600V
phase to earth, Category IV. Refer
to safety warnings supplied. |
EMC |
In accordance with IEC 61326
including amendment No.1 |
Temperature co-efficient |
<0,1% per °C up to 1 GΩ
<0,1% per °C per GΩ
above 1 GΩ |
Operating temperature
range and humidity |
-10 to +55 °C
90% RH at 40 °C max. |
Storage temperature range |
-25 to +70 °C |
Calibration temperature |
+20 °C |
Maximum altitude |
2000 m |
IP rating |