Resistance range |
0.01Ω to 200kΩ autoranging |
Analog model |
2.5% of scale length |
Digital models |
2P measurements 2% ±3 digits
3P measurements 2% ±3 digits
4P measurements 2% ±3 digits
ART measurements 5% ±3 digits
Stakeless measurements 7% ±3 digits |
Maximum probe resistance |
Rp limit: 100k½ (50V output voltage)
Rc limit: 100k½ (50V output voltage)
Limits reduced to 50k½ for 25V output voltage
Limits reduced to 5k½ for 0.01 ½ resolution |
Earth voltage range |
0 – 100 V |
Earth voltage accuracy |
2% ±2 V |
2-wire test |
Yes, all models |
3-wire test |
Yes, all models |
4-wire test |
DET4TD, DET4TC2, DET4TCR2 |
ART (Attached Rod Technique) |
DET3TC, DET4TC2 and DET4TCR2 |
Ground current range (with current measuring clamp) |
0.5 mA to 19.9 A |
Ground current accuracy |
5% ±3 digits |
Display |
LCD (moving coil meter for analog model) |
Test frequency |
128 Hz |
Test voltage |
25 V or 50 V, user selectable (factory setting 50 V) |
Test current |
450 micro-amps at 25 V or 50 V (selectable), 4.5mA at 25 V |
Noise rejection |
40V pk to pk |
Noise check |
Automatic (by selector switch DET3TA) |
C spike check |
Automatic (by pushbutton DET3TA) |
P spike check |
Automatic (by pushbutton DET3TA) |
Maximum current loop resistance |
100 k-ohms at 50V, 50 k-ohms at 25 V and 5 k-ohms for 0.01 ohm resolution for readings below 19 ohms |
Maximum voltage probe resistance |
100 k-ohms at 50V, 50 k-ohms at 25 V and 5 k-ohms for 0.01 ohm resolution for readings below 19 ohms |
Battery type |
8 1.5 V AA cells (8 1.5 V AA NiMH rechargeable cells – DET4TCR2) |
Battery life |
3 hours, 700 consecutive tests |
Safety |
EN61010-1 CAT IV 100 V |
Terminals |
4 mm plug type (test leads) |
Ingress protection |
IP54 |
EMC |
Meets the requirements of EN61326-1:1998 for use in heavy industrial areas |
Dimensions |
8 x 5.7 x 3.2 in. (203 x 148 x 78 mm) |
Weight |
2.2 lb (1 kg) |
Operating temperature range |
-.5º to +131º F (-15º to +55º C); DET3TA: -4º to +122º F (-20º to +50º C) |
Storage temperature range |
-40º to +158º F (-40º to +70º C) |
Humidity |
95% RH non-condensing at 104º F (40º C) |