Technical Specifications |
DC voltage |
Measuring range |
0.0V ÷ 999.9V |
Resolution |
0.1V |
Accuracy |
±(0.5%reading + 2digits) |
AC TRMS, DC, AC+DC TRMS, LoZ voltage |
Measuring range |
0.5V ÷ 999.9V |
Resolution |
0.1V |
Frequency range |
32Hz ÷ 1kHz |
Accuracy |
±(0.5%reading + 2digits) |
AC TRMS current with flexible clamp F3000U |
Measuring range |
1A ÷ 3000A |
Basic resolution |
0.01A |
Accuracy |
±(0.5%reading + 2digits) |
AC TRMS, DC, AC+DC TRMS current with standard clamp |
Measuring range |
1mV ÷ 1000mV |
Resolution |
1mV |
Accuracy |
±(0.5%reading + 2digits) |
Inrush current (DIRC) - Flexible clamp F3000U |
Measuring range |
1A ÷ 3000A |
Basic resolution |
0.01A |
Frequency range |
42.5Hz ÷ 69Hz |
Accuracy |
±(2.0%reading + 2digits) |
Response time of peak |
1ms |
Max RMS response time |
16.6ms, 20ms, 50ms, 100ms, 150ms, 175ms, 200ms |
Inrush current (DIRC) - Standard clamp |
Measuring range |
1mV ÷ 1000mV |
Resolution |
1mV |
Frequency range |
42.5Hz ÷ 69Hz |
Accuracy |
±(2.0%reading + 2digits) |
Response time of peak |
1ms |
Max RMS response time |
16.6ms, 20ms, 50ms, 100ms, 150ms, 175ms, 200ms |
Resistance and Continuity test |
Measuring range |
0.0Ω ÷ 1999Ω |
Basic resolution |
0.1Ω |
Accuracy |
±(1.0%reading + 5digits) |
Buzzer test |
R<30Ω |
Voltage / Current harmonics |
Harmonic order |
DC, 1st ÷ 25th + THD% |
Frequency range |
42.5Hz ÷ 69Hz |
Resolution |
0.1V / 0.1A |
Basic accuracy |
±(5.0%rdg + 10digits) |
Phase sequence with 1 terminal |
Measuring range |
100V ÷ 999.9V |
Frequency range |
42.5Hz ÷ 69Hz |
Insulation resistance |
Test voltages |
50,100,250,500,1000VDC |
Measuring range (@ 500V) |
0.01MΩ ÷ 999MΩ |
Resolution |
0.01MΩ ÷ 1MΩ |
Basic accuracy (@ 500V) |
±(2.0%reading + 2digits) |
Timer for measurements |
15s, 30s, 1min, 5min, 10min |
Continuity of protective conductors |
Test current |
>200mA DC (@ R<5Ω) |
Measuring range |
0.00Ω ÷ 199.9Ω |
Open-circuit voltage |
4 < Vo < 12V DC |
Accuracy |
±(2.0%reading + 2digits) |
General characteristics |
Instrument safety |
IEC/EN61010-1, IEC/EN61010-2-030, IEC/EN61010-2-033 |
EMC |
IEC/EN 61326-1 |
Test MΩ |
CEI 64-8, IEC/EN61557-2 |
Test LoΩ |
CEI 64-8, IEC/EN61557-4 |
Phase sequence |
IEC/EN 61557-7 |
Insulation |
double insulation |
Pollution level |
2 |
Measurement category |
CAT IV 600V, CAT III 1000V to earth and between inputs |
Mechanical characteristics |
Size (L x W x H) |
175 x 85 x 55mm |
Weight (batteries included) |
420g |
Mechanical protection |
IP40 |
Power supply |
Battery type |
4x1.5V batteries type AAA IEC LR03 |
Auto power off |
after 15 minutes’ idling |
Display |
Type of display |
4 dgt LCD, max 9999 dots, decimal sign, point, backlight and bargraph, indication of polarity |
Updating frequency |
2 times/s |