Measurement Accuracy |
Real Power and Energy |
IEC 62053-22 Class 0.5S, ANSI C12.20 0.5% |
Reactive Power and Energy |
IEC 62053-23 Class 2, 2% |
Current |
0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range |
Voltage |
0.4% (+0.015% per °C deviation from 25°C) from 90V (L-N) to 600VAC (LL) |
Sample Rate |
2520 samples per second |
Data Update Rate |
1 sec |
Type of Measurements |
True RMS up to the 21st harmonic 60 Hz, One to three phase AC system |
Input Voltage Characteristics |
Measured AC Voltage |
Minimum 90VL-N (156VL-L) for stated accuracy
UL Maximums: 600VL-L (347VL-N)
CE Maximums: 300VL-N (520V L-L) |
Metering Over Range |
+20% |
Impedance |
2.5 MΩ (L-N)/5 MΩ (L-L) |
Frequency Range |
45 to 65 Hz |
Input Current Characteristics |
CT Scaling |
Primary: Adjustable from 5 A to 32,000 A |
Measurement Input Range |
0 to 0.333VAC or 0 to 1.0VAC (+20% over-range) |
Impedance |
10.6kΩ (1/3 V mode) or 32.1kΩ (1 V mode) |
Output |
Alarm Contacts |
N.C., static output (30VAC/DC, 100mA max. @ 25°C, derate 0.56mA per °C above 25°C) |
Real/Reactive Energy Pulse Contacts |
N.O., static output (30VAC/DC, 100mA max. @ 25°C, |
derate 0.56mA per °C above 25°C) |
Mechanical Characteristics |
Weight |
0.62 lb (0.28 kg) |
IP Degree of Protection (IEC 60529) |
IP40 front display; IP20 Meter |
Display Characteristics |
Back-lit blue LCD |
Terminal Block Screw Torque |
0.37 ft•lb (0.5 N•m) nominal/0.44 ft-lb (0.6 N•m) max |
Terminal Block Wire Size |
26 to 14 AWG (0.13 to 2.08 mm2) |
Rail |
T35 (35mm) DIN Rail per EN50022 |
Environmental Conditions |
Operating Temperature |
Meter: -30° to 70°C; Display: 0° to 50°C |
Storage Temperature |
Meter: -40° to 85°C; Display: -10° to 60°C |
Humidity Range |
<95% RH (non-condensing) |
Altitude of Operation |
3 km max. |
Metering Category |
North America |
CAT III; for distribution systems up to 347 V L-N/600VAC L-L |
CE |
CAT III; for distribution systems up to 300 V L-N |
Dielectric Withstand |
Per UL 508, EN61010 |
Conducted and Radiated Emissions |
FCC part 15 Class B, EN55011/EN61000 Class B (residential and light industrial) |
Conducted and Radiated Immunity |
EN61000 Class A (heavy industrial) |
Safety |
North America (cULus) |
UL508 (open type device)/CSA 22.2 No. 14-05 |
Europe (CE) |
EN61010-1:2001 |