General Specifications |
Applicable Standards |
IEC 61000-4 / FCC part 15 / cULus 1778 Listed / ROhS |
MTBF (Each Module) |
240,000 hrs |
Efficiency (Typical): Enhanced Power Conversion / On Line |
94% / 90% |
Dielectric Strength DC/AC |
4,300 VDC |
True Redundant Systems - Compliant |
3 disconnection levels on AC out and DC in power ports
4 disconnection levels on AC in port |
Vibration |
GR63 office vibration 0 to 100 hz-0.1 g / transport vibration 5 – 100 Hz
0.5 g 100 – 500 Hz-1.5 g / Drop test |
Altitude Above Sea |
< 1,500 m no derating
> 1,500 m – 0.8 % derating per 100 m |
Ambient / Storage Temperature / Relative Humidity |
-40 – 70°C (-40 – 158°F) 95%, non-condensing |
Operating Temperature (Ambeint & Measured at Air Inlet) |
-20 – 40°C (-4 – 104°F) for rated power
40 – 65°C with 2% /°C derating
104 – 149 °F with 1% /°F derating |
Operating Environment / Ingress Protection |
Free from dust and corrosive materials |
Material (Casing) |
Coated steel-ALU ZINC |
DC Input Specifications |
Nominal Voltage (DC) / Voltage Range |
48 V / (40 – 58 V) |
Voltage Ripple |
< 2 mV Psopho |
Input Voltage Boundaries |
40 – 57 V user selectable |
DC Input Protections |
1 40 A MCB per module |
AC Input Specifications |
Voltage Range (AC) (Full Power Rating) |
100 – 140 VAC |
Brownout Range and Behavior |
80 – 104 VAC use DC source contribution if need be (can be disabled) |
Conformity Range Before Transfer to DC |
Adjustable from 80 – 138 VAC |
Power Factor |
>99% |
Frequency Range (Selectable) / Synchronization Range |
50 – 60 Hz / range 47 - 53 Hz / 57 - 63 Hz |
AC Output Specifications |
Admissible Load Power Factor |
Full VA power rating from 0 inductive to 0 capacitive
Limited to W power rating from Pf 0.8 to 1 |
Frequency / Frequency Accuracy |
50 – 60 Hz / 0.03 % |
Total Harmonic Distortion (Resistive Load) |
< 1.5 % |
Load Impact Recovery Time |
0.4 ms |
Turn On Delay |
30 s |
Short Duration Overload Capacity |
150% - 15 s |
Long Duration Overload Capacity |
110% permanent |
Crest Factor at Nominal Power with Short Circuit Management and Protection |
3.1 |
Short Circuit Clear Up Capacity 3 |
10 x in. for 20 ms |
Short Circuit Clear Up Capacity When AC is not Present |
1.5 x in. for 15s |
Energy Source Changeover |
Total Transient Voltage Duration (Max) (As See From the Load) |
0 s (and no glitch) |
Maintenance Bypass (MBP) |
No |
Signaling & Supervision |
Display |
LED w/module status and power bargraph + [OPTIONAL] CANDIS Display (1/ph) |
Alarms Output / Supervision |
No.3 Dry Contacts (Maj, Min, User adj) |
Remote Monitoring |
(OPTIONAL) TCP-IP with SNMP V1 |
Remote On / Off |
via T2S controller |