Toll Free: (877) 571-7901
Local: (732) 728-2590
salesteam@tequipment.net
My Account
Sign in to see your member price, rewards, orders, tracking and more.
Why Join? Gain access to exclusive pricing, rewards and more!
Member Pricing & Rewards active
(877) 571-7901
Sales@TEquipment.NET
Member Pricing & Rewards are active.
Accurate measurements without the need to precisely position wire or cable in the center of the jaw clamp.SHOP NOW
The SDS3104XHD features an impressive array of measurement and math capabilities, options for a 50 MHz arbitrary waveform generator, as well as serial decoding. SHOP NOW
The Megger IMT100 is the most versatile multi-tester for PV systems, electric vehicles and industrial applications.SHOP NOW
Similar Items
Let us quote you our best price!
Allow us to earn your business and make this purchase easy.
0 reviews | Model: Eagle Eye LB-480-200-CCS
480V, 200A Constant Current Load Bank with Data, Software and Per Cell Moni
List Price: $32,194.00
We accept purchase orders and all major credit cards. We also provide financing via Klarna at checkout for qualifying purchases.
Have a question or need to apply for payment terms?
Contact us.
Have a question? Ask an expert.
Eagle Eye’s LB-Series Constant Current DC Load Banks are designed for discharge testing, battery capacity testing, acceptance testing, battery maintenance, and other testing of DC systems. The LB-Series Constant Current Load Banks are portable, economic, reliable and user-friendly. With over (100) standard models and an operating range of 5 – 600V / 0 – 2000A. The intelligent technology allows a constant current discharge without the need for any adjustments during the test. The LB-Series is essential in a variety of industries including utilities, telecommunications, UPS, motive power / forklifts, transportation, CATV, and many more. The intelligent technology allows a constant current discharge without the need for any adjustments during the test.
Eagle Eye’s comprehensive software package enables users to monitor discharge events in real time, record data, analyze, remote start & stop tests, and create reports. Reports are exported to Microsoft Excel or Word and can be customized by the user to add company name, location, battery details, and more. Both the raw test data values are available, along with visual graphs for viewing both per cell and string information. Information includes per cell voltages, string voltages, and discharge current from each user-selected data interval. Intervals can be set to as low as every 3 seconds, depending on your test length.
What safety cutoffs do the LB-Series Constant Current load banks have?
Answers (1) - Asked by Anonymous
I have this question too (0)
The DC load bank will shut down based on user adjustable settings of time, string voltage, and capacity. It also has thermal protection shutdown.
I found this helpful (0)
Inaccurate? (0)
Answered by Anonymous
What is meant by constant current?
Constant current means that the load bank will deliver a constant load set by the user from the beginning to end of a load test regardless of the drop in voltage.
Is the load bank able to discharge strings in parallel?
As long as the nominal voltage falls within the working voltage of the specific unit the load tester will be able to discharge parallel strings.
Are the LB-Series constant current load banks compatible with online applications?
Yes, the constant current load bank could be used in an online application however we do not recommend this practice unless testing the performance of the charger / rectifier as discharging the batteries while connected to a load source leaves the batteries vulnerable for system failure.