Model: ASL-L01SP1-PY Specifications |
Description |
ASL Series Solid State Relay Terminal Block (Screwless Type) |
Power supply |
24VDC=±10% |
Rated load voltage & current※2 |
75-240VAC~50/60Hz 2A |
Current consumption※3 |
≤ 18mA |
Output type |
1a contact relay output |
Applied SSR |
AQG22124 [Panasonic] |
Terminal type |
Screwless |
Terminal pitch |
1-point: 9.0mm (arranging over 2 units)/4-point: 5.0mm |
Operation Indicator |
Blue LED |
Applied cable |
Solid wire |
Ø0.6 to Ø1.25mm (60℃ only) |
Stranded wire※4 |
AWG22-16 (0.30 to 1.25mm 2 ) (60℃ only) |
Stripped wire length |
8 to 10mm |
Insulation resistance |
1-point: ≥ 1,000MΩ (at 500VDC megger)/4-point: ≥ 1,000MΩ (at 500VDC megger) |
Insulation resistance |
Between coil-contact |
2,500VAC 50/60Hz for 1 minute |
Between same contacts※ 5 |
1,000VAC 50/60Hz for 1 minute |
Vibration |
Mechanical |
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours |
Malfunction |
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 minutes |
Shock |
Mechanical |
1,000m/s 2 (approx. 100G) in each X, Y, Z direction for 3 times |
Malfunction |
100m/s 2 (approx. 10G) in each X, Y, Z direction for 3 times |
Environment |
Ambient temp. |
-15 to 55℃, storage: -25 to 65℃ |
Ambient humi. |
35 to 85%RH, storage: 35 to 85%RH |
Material |
Terminal block: polyamide 66, conducting plate: brass, case&base: poly phenylene sulfide |
Accessory |
Jumper bar: 1 |
Protection structure |
IP20 (IEC standard) |
Weight※7 |
Approx. 140g
(approx. 22g) |
※1: This is for load protection and it is recommend to use at the inductive load. |
※2: This is relay load capacity when it is resistive load and temperature characteristic curve is satisfied. |
※3: The current consumption including LED current by one relay. |
※4: When using stranded wire, use End Sleeve (ferrule terminal) crimp terminals. |
※5: ASL-L01 - Y/ASL-L04 - Y (varistor installed type), this is 300VAC. |
※6: Ejector is supplied only for ASL-L04 - (4-point). |
※7: The weight includes packaging. The weight in parenthesis is for unit only. |
※8: The weight of 1-point unit is per 4 units with packaging and the weight of parenthesis is per 1. |
※Environment resistance is rated at no freezing or condensation. |