company logo Megger DET20C Down Loading Ground Resistance Clamp Tester
     Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.  
 
 
 



Megger DET20C Down Loading Ground Resistance Clamp Tester




Click image to enlarge

Megger DET20C

Data Sheet
Application Guide
User Guide

Features:
  • Easy and fast clamp-on operation. No need for cables or auxiliary rods/stakes.
  • Large LCD display screen that can be read in bright sunlight.
  • Measures ground resistance from 0.025Ω to 1550Ω.
  • Direct reading of continuity and ground loop resistance.
  • Measures ground leakage or phase current from 0.2mA to 25A.
  • Large jaw opening to accommodate a variety of conductors.
  • Indication of high noise content that may affect readings.
  • Lightweight...only 750g (1.65lbs), yet exceptionally rugged for regular field use.
  • Hold function for difficult to reach installations.
  • Auto-off to save on battery power.
  • Configure high and low alarms with audible indication for fast field checks.
  • On board storage of test results (up to 8180 records).
  • Calibration check loop to insure proper operation.
  • Rugged, yet lightweight storage case contains complete testing kit.
  • RS-232 interface for download of test data for later analysis (DET20C).

Applications:

The DET10C and 20C have a variety of applications including:

  • Use to measure resistance and continuity of grounding loops around pads and buildings.
  • Use on multi-grounded systems without disconnecting the ground rod/stake under test.
  • Use to measure leakage current flowing to ground or circulating in ground systems.
  • Use on cell towers, RF transmitters and telecommunications sites.
  • Use to inspect and verify lightning protection systems.
  • Use on a variety of consumer installations, including pools, spas, etc.



  Description

The Megger models DET10C and 20C measure earth/ground resistance and current flow using clamp-on technology. The instruments induce a test current into the system without the need to disturb existing connections. Either unit is a useful addition to the more traditional methods of earth/ground resistance testing that may require disconnection and the use of stakes or ground rods. Simply clamp around the conductor or stake/rod and measure the resistance to ground fast and accurately.

The DET10C and 20C can also be used to measure earth/ground resistance in multiple loop installations without disconnecting the earth or ground. This allows the user to perform the test quickly and easily in total safety, with the added convenience of having a single point of measurement to read the earth/ground resistance.

Each instrument also provides a true RMS current measurement reading to better indicate potential measurement problems and provide a useful overview of the dynamics of the general earth/ground system.

The units are rugged, compact and have configurable audible alarms. They also feature auto shutdown (which is also configurable), data storage and self calibration on power-up, and are supplied with a calibration loop – all contained in a rugged carry case. The DET20C also comes with a RS232 interface cable and is compatible with Megger Download Manager Software (included) allowing further analysis and storage of data.

DET20C OPERATION DET20C DISPLAY EXAMPLE

Click image to enlarge

Click image to enlarge
DET20C Data Functions
• Store a specific reading
• Data logging
• Adjustable sampling interval
• Data logging capacity up to 8180 records (DET20C)
• Review of stored data
• Download data to a PC for later analysis



  Additional Photos:
 

Click image to enlarge

Click image to enlarge

Click image to enlarge


  Models, Options, & Accessories


Model Description List Price Sale Price
DET20C Clamp-On Ground Tester with Data Storage $1660.00
$1577.00 
DET10C Clamp-On Ground Tester $1500.00
$1425.00 



  Specifications

Ground Resistance
Range*2
Resolution
Accuracy*1
0.025 - 0.25Ω
0.002Ω
± 1.5% ± 0.05Ω
0.25 - 9.999Ω
0.02Ω
± 1.5% ± 0.1Ω
10 - 99.99Ω
0.04Ω
± 2.0% ± 0.3Ω
100 - 199.9Ω
0.4Ω
± 3.0% ± 1.0Ω
200 - 400Ω
± 5.0% ± 5Ω
400 - 600Ω
± 10% ± 10Ω
600 - 1550Ω
20Ω
± 20%
1- Loop resistance non-inductive, external field <50 A/m, external electrical field <1 V/m, onductor centred in jaws.
2- Resistance measurement frequency 1.667KHz

Alarm Type
Range
Resolution
High Alarm
0 - 1550Ω
Low Alarm
0 - 1550Ω

Leakage Current
Range*3
Resolution
Accuracy
0.200 – 1.000 mA
0.001 mA
± 2.0% ± 0.05 mA
1.00 – 10.00 mA
0.01 mA
± 2.0% ± 0.03 mA
10.0 – 100.0 mA
0.1 mA
± 2.0% ± 0.3 mA
100 – 1000 mA
1 mA
± 2.0% ± 3 mA
0.20 – 35 A
0.01 A
± 2.0% ± 0.03 A
3- Auto range, 50/60Hz, true RMS to crest factor <3.5

Conductor Size 35mm Ø approx
Battery Type 9V IEC 6 LR61 alkaline
Display Type ±1%
Range Selection 18 H x 30 W x 19.5 D in.
(457 H x 762 W x 495 D mm)
Overload Indication 15.5 H x 30 W x 19.5 D in.
(394 H x 762 W x 495 D mm)
Power Consumption 4 digits 9999 counts LCD
Battery Life Automatic within function
Auto Power Down OL
Sampling Time 0.5 seconds
Operating Ttemperature 0 to 50º C
Storage Temperature -20º C to 60º C
Operating Humidity Less than 85% RH
Storage Humidity Less than 75% RH
Dimensions 276 L X 100 W X 47 H (mm)
Weight 750g (1.65lbs)
Date Logging Capacity DET10C 116 records
Data Logging Capacity DET20C 8180 records
Saftey
EN61010-2-032
CATIII 300 V, CATII 600 V
Pollution degree 2



 

Welcome | Companies | Search by Type | How To Order | Leasing | About Us | Careers
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
BBBOnline Reliability Seal, Click for confirmation page. Tequipment.NET
Phone: 1-877-571-7901 / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET
 




Megger 110% Price Match Guarantee

Quote Request

We Take POs, How To Order

Free Shipping on Megger










Live chat by BoldChat
Need help? We have a staff
of more than 30 people to help you.
Let us show you why over 100,000
customers choose Tequipment.NET