Megger BM21 5 kV Analog/Digital Insulation Testers

Click image to enlarge
Megger BM21 |
Data
Sheet |
Features:
- Choice of test voltages
- Direct reading display
- Unique rugged case
- Guard terminal
- Designed for user safety
- Large, custom Analog/Digital LCD
- Built-in timer
- Locking test leads for safety
- Battery indicator
- Automatic discharge of capacitance
- Voltage measurement and warning
- Tests to 500 G½
- Weather proof to IP54
- Variable test voltage in 25 V steps
- Breakdown or ‘Burn’ modes allow
choice of diagnostic approach
- Shows capacitance at end of test
- Timer sets test duration for easier test
control
- Tests to 5,000 G½
- Leakage current mode
Applications:
The BM11 series is designed for testing the
insulation of high voltage electrical equipment and the wide voltage
range also allows it to be applied to low voltage equipment.
Generators, motors, transformers, cables and
switchgear all require effective maintenance and the test techniques
on the Megger range give valuable diagnostic information.
‘Spot’ Insulation tests that are
the most widely used, check on the general condition of electrical
insulation, called up in most standards covering equipment design,
testing, installation and maintenance.
Insulation suffers from gradual steady decline,
as well as occasional sudden damage; the effects of dirt, grease,
moisture, vibration and chemical attack can be tracked through
the recording of Polarisation Index tests which remove the temperature
dependence of raw Insulation Resistance measurements.
For finding more localised insulation problems,
the BM25 includes both Step Voltage and Dielectric Discharge tests.
Step Voltage identifies local weak spots because they respond
differently as the electrical stress is increased, while the Dielectric
Discharge test can show up a single bad layer in multilayer insulation.
The key to Predictive maintenance is the trending of diagnostic
tests and this is facilitated on the BM25 by the ability to use
a PC to store results over time for trend analysis.
|
Description
The Megger® BM11 series of 5 kV
Insulation Testers provides a choice of features to suit all applications
and budgets.
The traditional BM11 instrument became the industrystandard 5
kV tester. It is battery-powered, housed in a rugged case and
has a large, simple white-on-black scale.
The series has been extended with three Analog/digital instruments;
the BM11D, BM21 and BM25. These instruments show results and test
options on a large, clear Analog/digital scale for both practicality
and precision. A built-in timer makes both spot tests and PI testing
easier to carry out.
They are powered by a built-in rechargeable lead-acid battery
which can be charged directly from any supply from 95 V to 265
V. All testers incorporate a guard terminal to allow surface leakage
to be removed.
Pre-set standard test voltages at 500 V, 1000 V, 2500 V and 5000
V are supplemented on the BM21 and BM25 units with a variable
test voltage in 25 V steps. These top of the range units also
allow measurement of resistance to 5 T½, leakage current
to 0,01 nA and can display capacitance at the end of a test to
10 µF.
The BM25 extends the diagnostic testing capability of the range
by performing automatic Polarisation Index, Step Voltage and Dielectric
Discharge tests as well as providing an optically isolated RS232
port for downloading results during a test.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| BM21 |
Analog/Digital 5 kV Megger; 500, 1000, 2500, 5000 V; 5 TOhms (218621) - Discontinued - replaced by Megger MIT520/2 |
| BM11 |
Analog 5 kV Megger Insulation Tester; 500, 1000, 2500, 5000 V; 100 GOhms (218650) - Discontinued - replaced by Megger MIT510/2 |
| BM11D |
Analog/Digital 5 kV Megger; 500, 1000, 2500, 5000 V; 1 TOhms (218651) - Discontinued - replaced by Megger MIT510/2 |
| BM25 |
Analog/Digital 5 kV Megger; 500, 1000, 2500, 5000 V; 5 TOhms - Discontinued - replaced by Megger MIT520/2 |
| Model |
Accessories |
List Price |
Sale Price |
| 8101-181 |
Set of Three 10 ft. Leads for 218651, 218621, BM25, BM15 & MJ15 |
$225.00 |
| $213.75 |  |
|
| 25424-860 |
Please call or email us for pricing and availability. |
| 6430-193 |
Please call or email us for pricing and availability. |
| 6172-922 |
Please call or email us for pricing and availability. |
| 6121-291 |
Please call or email us for pricing and availability. |
| 25424-860 |
Please call or email us for pricing and availability. |
| 6420-096 |
Please call or email us for pricing and availability. |
| 25955-025 |
Please call or email us for pricing and availability. |
| 6139-085 |
Please call or email us for pricing and availability. |
| 6172-112 |
Please call or email us for pricing and availability. |
| 6220-318 |
Please call or email us for pricing and availability. |
| 8101-182 |
Set of 25 ft. leads for the MIT5/10 Series |
$320.00 |
| $304.00 |  |
|
| 8101-183 |
Set of 50 ft. (15 m) leads for the MIT5/10 Series |
$365.00 |
| $346.75 |  |
|
| 6231-584 |
Please call or email us for pricing and availability. |
| 6311-077 |
Please call or email us for pricing and availability. |
| 6111-217 |
Please call or email us for pricing and availability. |
| AVTM21-P8B |
Please call or email us for pricing and availability. |
| AVTM22P-1 |
H.V Test Guide |
$50.00 |
| $47.50 |  |
|
| 6111-287 |
Please call or email us for pricing and availability. |
Specifications
| Test voltages |
500, 1000, 2500, 5000 V; plus 25 to 5000
V in 25 V steps |
| Accuracy |
±5% on 100 M½ load ±25V
for test voltages <500V |
| Insulation Resistance Range |
Digital 10 k½ to 500 G½ @ 500
V
10 k½ to 1 T½ @ 1000 V
10 k½ to 2,5 T½ @ 2500 V
10 k½ to 5 T½ @ 5 kV
Analog 100 k½ to 1T½ @ all voltages |
| Basic Accuracy |
±5% of reading 1M½ to 1 T½
@ 5 kV (0 to 30°C)
(32 to 86°F) |
| Short Circuit Current |
1,8 mA nominal, 2 mA max. |
| Voltage Range Accuracy (20°C) |
50 to 1000 V d.c. or a.c. (0 to 5000 V d.c.
when testing)
Accuracy ±2%, ±1 V |
| Display |
Analog/digital (3 digits) |
| Interference Rejection |
1 mA r.m.s. per kV to a maximum 2 mA |
| Capacitor Discharge Time |
< 2 s per µF to discharge from 5000
V to 50 V |
| Leakage current measurement |
0,01 nA to 999 µA Accuracy ±5% ±0,2
nA |
| Capacitancemeasurement |
0,01 - 10,0 µF (displayed at end of
test) Accuracy ±15% ±0,03 µF |
| Timer |
User selectable 0 to 90 minutes
Test is terminated at end of preset time |
| Temperature Range |
Operating -20to +50°C (-4 to 122°F)
Storage -25°C to +65°C (-13 to 149°F) |
| Temperature Coefficient |
(Applies over range 0 to 30°C)
0,2% per °C for test currents >100 nA (0.1%/°F)
0,1% per °C for test voltage (0.05%/°F) |
| Humidity Range |
90% RH @ 40°C max. (104°F) |
| Safety |
EC1010-1 (1995), EN61010 (1995) to installation
category III, 300 V, phase to earth, 500 V phase to phase |
|