Features:
Installing the 9605 HARMONIC/FLICKER MEASUREMENTS UNIT in a 3193
POWER HiTESTER adds the following functions to the basic functions of the
3193.
- Support for range of power lines
- Support for IEC1000-3-2 analysis method
- Range of display options (harmonic analysis function)
- Waveform display (harmonic analysis function)
- Floppy disk support
- Built-in printer (option)
|
Description
|
Installing the 9605 HARMONIC/FLICKER MEASUREMENTS UNIT in a 3193
POWER HiTESTER enables voltage, current, and power harmonic analysis
and flicker measurement to be carried out on the voltage and current
waveforms captured by an input unit, for single phase to three-phase fourwire
lines. It also provides list, a range of display options, including graph
and vector displays.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 9605 |
Harmonics/Flicker Unit (3193) |
| $1895.00 |  |
|
General Specifications
| Application |
Fitted in a 3193 unit (factory-fitted option) |
| Measurement lines |
Single-phase,two-wire (1P2W)/ Single-phase,three-wire (1P3W)/ Threephase, three-wire (3V3A, 3P3W)/ Three-phase,four-wire (3P4W) |
| Number of channels |
Maximum of 3 channels selectable from channels 1 to 6, depending on 3193 unit wiring mode
| |
1ch |
2ch |
3ch |
4ch |
5ch |
6ch |
Using Channels |
| 1 |
1P2W |
1P2W |
1P2W |
1P2W |
1P2W |
1P2W |
1+2+3, 2+3+4, 3+4+5, 4+5+6 |
| 2 |
1P3W/3P3W |
1P2W |
1P2W |
1P2W |
1P2W |
12+3, 3+4+5, 4+5+6 |
| 3 |
1P3W/3P3W |
1P3W/3P3W |
1P2W |
1P2W |
12+3, 34+5, 4+5+6 |
| 4 |
1P3W/3P3W |
1P3W/3P3W |
1P3W/3P3W |
12+3, 34+5, 56 |
| 5 |
3V3A/3P4W |
1P2W |
1P2W |
1P2W |
123, 4+5+6 |
| 6 |
3V3A/3P4W |
1P3W/3P3W |
1P2W |
123, 45+6 |
| 7 |
3V3A/3P4W |
3V3A/3P4W |
123, 456 |
|
| Measurement range |
Basic frequency 1 to 440 Hz, external clock type: 1 to 5 Hz, PLL type: 5 to 440 Hz
For fundamental from 45 Hz to 66 Hz, measurement is compliant with
IEC61000-3-2 and MITI guidelines (constant measurement / fluctuating
measurement), except no 2.5-minute fluctuating measurement or waveform
decision function.
|
| Measurement system |
PLL synchronization
For fundamental from 45 Hz to 66 Hz, fundamental frequency and PLL
synchronizing frequency phase deviation no more than 0.01%
|
| Analysis method |
FFT |
| Type of window |
Rectangular (no gaps or overlaps in window) |
| Display update rate |
Every 1 window (excluding when FFD/printer output and communication) |
| A/D |
16 bits |
| Computational accuracy |
32 bits (floating-point calculations) |
| PLL source |
Select voltage (U) or current (I) from the channel combination selected for measurement |
| External clock signal |
Input clock signal of frequency ((measured signal frequency) 8192 256) (TTL levels) enables measurement in the low-frequency range (1 Hz to 5 Hz) |
| Crest factor |
4 max. (current), 3 max. (voltage) |
| Output function |
FD, printer,GP-IB, RS-232C |
| Sampling rate |
External clock input frequency: (1 to 5 Hz) 8192 256
Analysis harmonic order: 50th
Window width: 1 cycle
| Basic input frequency |
Sampling rate |
Analysis harmonic order |
Window width |
| 5 to 10 Hz |
f×4096 |
50th |
2 cycles |
| 10 to 20 Hz |
f×2048 |
50th |
4 cycles |
| 20 to 40 Hz |
f×1024 |
50th |
8 cycles |
| 40 to 70 Hz |
f×512 |
50th |
16 cycles |
| 70 to 140 Hz |
f×256 |
50th |
32 cycles |
| 140 to 250 Hz |
f×128 |
50th |
64 cycles |
| 250 to 440 Hz |
f×64 |
27th |
128 cycles |
|
|